AS NZS 60079.17:2017 pdf free

09-04 comment

AS NZS 60079.17:2017 pdf free.Explosive atmospheres Part 17: Electrical installations inspection and maintenance.
4 General requirements
4.1 Documentation
For the purposes of inspection and maintenance, up-to-date documentation (verification dossier) including any modification records, of the following items shall be available:
a) zone classification of areas and, if included, the equipment protection level (EPL) required for each location (see lEG 60079-10-1 and IEC 60079-10-2),
b) for gases: equipment group (IIA, llB or IIC) and temperature class requirements,
C) for dusts: equipment group (lIlA, lllB or IIIC) and maximum surface temperature requirements,
d) equipment characteristics e.g. temperature ratings, type of protection, IP rating, corrosion resistance,
e) records sufficient to enable the explosion protected equipment to be maintained in accordance with its type of protection (see IEC 60079-14), (for example list and location of equipment, spares, certificates, technical information),
f) copies of previous inspection records,
g) copy of the additional initial inspection records as detailed in IEC 60079-14.
Requirements for other documentation that may be necessary are provided in lEG 60079-14
and IEC 60079-19.
4.2 Qualification of personnel
The inspection and maintenance of installations covered by this standard shall be carried out only by experienced personnel, whose training has included instruction on the various types of protection and installation practices, the requirements of this standard, the relevant national regulations/company rules applicable to the installation and on the general principles of area classification (see Annex B). Appropriate continuing education or training shall be undertaken by personnel on a regular basis. Evidence of the relevant experience and training claimed shall be documented and available.
4.3 Inspections
4.3.1 General
4.3.1.1 Basic Principles
Before plant or equipment is brought into service, it shall be given an initial inspection. As part of the plant commissioning and start up procedures, initial inspection and other additional requirements are provided in IEC 60079-14.
To ensure that the installations are maintained in a satisfactory condition for continued use within a hazardous area, either
a) regular periodic inspections, or
b) continuous supervision by skilled personnel,
and, where necessary, maintenance shall be carried out.
NOTE 1 In the case of dusts, fibres or flyings, housekeeping can influence the inspection and maintenance requirements.
Following any adjustment, maintenance, repair, reclamation, modification or replacement, the equipment or relevant parts of equipment concerned shall be inspected in accordance with the relevant items of the detailed column of Tables 1, 2 and 3.AS NZS 60079.17 pdf download.

Download It Now Download Here
ATTENTION: I REALLY NEED YOUR SUPPORT.THANKS A LOT.
AS NZS 60598.2.17:2019 AS pdf free download

AS NZS 60598.2.17:2019

AS NZS 60598.2.17:2019 pdf free.Luminaires Part 2.17: Particular requirements—Luminaires for stage lighting, television and film studios (outdoor and indoor). 17.7.2 The luminaires for certain types of high-intensity discharge lamp, where an explosion risk is declared by the lamp manufacturer, shall incorporate a device to prevent immediate access to the lamp after switching-off or shall be marked in accordance with the...
Download
AS NZS 4859.1:2018 AS pdf free download

AS NZS 4859.1:2018

AS NZS 4859.1:2018 pdf free.Thermal insulation materials for buildings Part 1: General criteria and technical provisions. 2.1 GENERAL This Section provides performance criteria and technical provisions for materials to be used in the thermal insulation of buildings and building services. In addition to this Section the insulating material shall— (a) meet packaging and labelling requirements of Section 3; (b) where...
Download
AS NZS 2442.2:2021 AS pdf free download

AS NZS 2442.2:2021

AS NZS 2442.2:2021 pdf free.Performance of household electrical appliances一Rotary clothes dryers Part 2: Energy efficiency labelling requirements. Section 2 Test requirements, calculations and algorithms for the energy rating label 2.1 General This Section sets out the test requirements, equations and procedures br calculating values of the comparative energy consumption (CEC), and star rating, which appear on an energy rating label....
Download

LEAVE A REPLY

Anonymous netizen Fill in information