AS NZS IEC 60332.1.1:2017 pdf free download Tests on electric and optical fibre cables under fire conditions Part 1.1: Test for vertical flame propagation for a single insulated wire or cable- Apparatus

09-04 comment

AS NZS IEC 60332.1.1:2017 pdf free download. Tests on electric and optical fibre cables under fire conditions Part 1.1: Test for vertical flame propagation for a single insulated wire or cable- Apparatus.
5.4 Flame application
Safety warning
Precautions shall be taken to safeguard personnel against the following when conducting tests:
a) the risk of fire or explosion;
b) the inhalation of smoke and/or noxious products, particularly when halogenated materials are burned;
c) harmful residues.
5.4.1 Positioning of flame
A burner, as described in IEC 60332-1-1, shall be ignited and the flow rates of gas and air adjusted to the specified values. The burner shall be positioned so that the tip of the blue cone impinges on the surface of the test piece at a distance of (475 ± 5) mm from the lower edge of the upper horizontal support, whilst the burner is at an angle of (45 ± 2°) to the vertical axis of the test piece (see Figure 2). The burner position shall be fixed throughout the flame application time.
For flat-form cables, the flame impingement shall be on the middle of the flat side of the cable.
In case of an electrical insulated conductor or cable, should the test piece move significantly during the test so as to render the result invalid, the test piece shall be held straight by the attachment of a load of approximately 5 N/mm2 of conductor area to the lower part of the sample so that the distance between the point where the load is attached and the lower edge of the top support measures (550 ± 5) mm. In such cases, the test piece shall not be secured to the lower support.
5.4.2 Test duration
The flame shall be applied continuously for the period of time corresponding to the diameter shown in Table 1.
At the end of the specified flame application time, the burner shall be removed and the flame of the burner extinguished.
6 Evaluation of test results
During the test duration, it shall be recorded:
a) if the filter paper has ignited or not;
b) if the filter paper has ignited, the time from ignition of the filter paper to cessation of the burning.AS NZS IEC 60332.1.1 pdf download.

Download It Now Download Here
ATTENTION: I REALLY NEED YOUR SUPPORT.THANKS A LOT.
AS NZS 60598.2.17:2019 AS pdf free download

AS NZS 60598.2.17:2019

AS NZS 60598.2.17:2019 pdf free.Luminaires Part 2.17: Particular requirements—Luminaires for stage lighting, television and film studios (outdoor and indoor). 17.7.2 The luminaires for certain types of high-intensity discharge lamp, where an explosion risk is declared by the lamp manufacturer, shall incorporate a device to prevent immediate access to the lamp after switching-off or shall be marked in accordance with the...
Download
AS NZS 4859.1:2018 AS pdf free download

AS NZS 4859.1:2018

AS NZS 4859.1:2018 pdf free.Thermal insulation materials for buildings Part 1: General criteria and technical provisions. 2.1 GENERAL This Section provides performance criteria and technical provisions for materials to be used in the thermal insulation of buildings and building services. In addition to this Section the insulating material shall— (a) meet packaging and labelling requirements of Section 3; (b) where...
Download
AS NZS 2442.2:2021 AS pdf free download

AS NZS 2442.2:2021

AS NZS 2442.2:2021 pdf free.Performance of household electrical appliances一Rotary clothes dryers Part 2: Energy efficiency labelling requirements. Section 2 Test requirements, calculations and algorithms for the energy rating label 2.1 General This Section sets out the test requirements, equations and procedures br calculating values of the comparative energy consumption (CEC), and star rating, which appear on an energy rating label....
Download

LEAVE A REPLY

Anonymous netizen Fill in information