AS 4487 Amdt 1-2017 pdf free.Condensed aerosol fire extinguishing systems—Requirements for system design, installation and commissioning and test methods for components.
Clause 7.7.4
Delete the clause text (including Note) and replace with the following:
Warning notices shall have black lettering on a yellow background with a letter size equal to or greater than that detailed in Figures 1, 2 and 3 (when this document is printed in full size on A4 paper). Notices shall be provided at the following locations:
(a) At all entrances to the protected enclosure (see Figures 1 and 3).
(b) At each local control station (see Figure 2).
(c) At each automatic/manual switch (see Figure 3).
NOTE: The notice in Figure 3 is complementary to the notice in Figure 1 and should be located next to it.
Figure 1
Delete the Figure caption and replace with the following:
FIGURE 1 TYPICAL WARNING NOTICE TO BE DISPLAYED AT EACH ENTRY TO
THE PROTECTED AREA OR ENCLOSURE
Figure 2
Delete the Figure caption and replace with the following:
FIGURE 2 TYPICAL WARNING NOTICE TO BE DISPLAYED AT THE
MANUAL RELEASE
Clause 8.2.1
Delete the ‘WARNING’ and replace with the following:
VARNlNG: AN AUTOMATIC/MANUAL SWITCH SHALL BE OPERATED
PRIOR TO ENTERING THE PROTECTED ENCLOSURE.
Clause 8.2.6
Delete the clause text and replace with the following:
System functional testing shall be in accordance with the commissioning section of AS 1670.1 and shall include the following:
(a) Operate the detection initiating circuit(s). Verify that all alarm functions occur according to the design specifications.
(b) Operate the necessary circuit to initiate a second alarm circuit if present. Verify that all second alarm functions occur according to design specifications.
(c) Operate the discharge manual control. Verify that functions associated with manual discharge occur according to design specifications.
(d) Test all system interfaces function as intended, e.g. air handling systems, dampers, equipment shutdown.
(e) Where installed, operate the automatic/manual switch. Verify that functions occur according to the design specifications. Confirm that visual and audible supervisory signals are received at the control panel.
(f) Check pneumatic equipment, where fitted, for integrity to ensure proper operation.AS 4487 Amdt 1 pdf download.

Download It Now Download Here
ATTENTION: I REALLY NEED YOUR SUPPORT.THANKS A LOT.
AS NZS 60598.2.17:2019 AS pdf free download

AS NZS 60598.2.17:2019

AS NZS 60598.2.17:2019 pdf free.Luminaires Part 2.17: Particular requirements—Luminaires for stage lighting, television and film studios (outdoor and indoor). 17.7.2 The luminaires for certain types of high-intensity discharge lamp, where an explosion risk is declared by the lamp manufacturer, shall incorporate a device to prevent immediate access to the lamp after switching-off or shall be marked in accordance with the...
Download
AS NZS 4859.1:2018 AS pdf free download

AS NZS 4859.1:2018

AS NZS 4859.1:2018 pdf free.Thermal insulation materials for buildings Part 1: General criteria and technical provisions. 2.1 GENERAL This Section provides performance criteria and technical provisions for materials to be used in the thermal insulation of buildings and building services. In addition to this Section the insulating material shall— (a) meet packaging and labelling requirements of Section 3; (b) where...
Download
AS NZS 2442.2:2021 AS pdf free download

AS NZS 2442.2:2021

AS NZS 2442.2:2021 pdf free.Performance of household electrical appliances一Rotary clothes dryers Part 2: Energy efficiency labelling requirements. Section 2 Test requirements, calculations and algorithms for the energy rating label 2.1 General This Section sets out the test requirements, equations and procedures br calculating values of the comparative energy consumption (CEC), and star rating, which appear on an energy rating label....
Download

LEAVE A REPLY

Anonymous netizen Fill in information