AS 1603.11:2018 pdf free.Automatic fire detection and alarm systems Part 11: Visual warning devices.
2.3 Luminance requirements for LED matrix, fixed message type VWD
2.3.1 Mean luminance
The mean luminance for LED matrix VWD shall be not less than 180 cd/rn2.
2.3.2 Uniformity
The ratio of maximum luminance to minimum luminance across the VWD shall be not less than 100:1 for character to background contrast.
Character to character uniformity shall provide a luminance differential of not more than ± 10 %.
2.4 Luminance requirements for programmable message type VWD
2.4.1 Mean luminance
The mean luminance for programmable message type VWD shall be not less than 180 cd/rn2.
2.4.2 Uniformity
The ratio of maximum luminance to minimum luminance across the VWD shall be not less than 10 0:1 for character to background contrast.
Character to character uniformity shall provide a luminance differential of not more than ± 10 %.
2.4.3 Flashing messages
For programmable message type VWD intended to flash in the alarm mode, or containing an attention- getting phase, the message shall remain constant while the VWD is flashing. Where the whole message cannot be viewed during the scrolling phase, it shall not flash.
2.4.4 Fire safety text messages
Representative text messages related to fire safety shall be provided and meet the requirements of Clauses 2.4.1, 2.4.2 and 2.4.3.
NOTE Message length and repetition timing should be considered.
2.5 Maximum rated viewing distance
The rated maximum viewing distance for the displayed characters shall be calculated based on an angle subtended by the eye of 18 mm of arc at the rated viewing distance.
2.12 Remotely controlled VWD
Where the VWD forms part of a fire detection and alarm system or emergency warning system and include interface equipment for remote control, the interface shall meet the requirements of at least one of the following pieces of equipment:
(a) An I/O Device conforming to AS 150 7240.18.
(b) A distributed part of control and indicating equipment (CIE) conforming to the relevant parts of AS 4428.16 or AS 7240.2.
2.13 Construction
2.13.1 Visual warning text contrast
Lettering shall be in a contrasting colour to the background.
2.13.2 Connecting facilities
The means of connection shall not permit removal of the VWD without initiating a fault signal at the CIE. Where this requirement can be achieved without providing a separate termination for each incoming and outgoing conductor, such alternative means of connection shall be considered satisfactory. This requirement includes any arrangement by which the VWD can be detached from its terminating facility.
The terminations shall be designed so that any connected conductors can be rigidly and effectively clamped between metal surfaces, or soldered, to ensure the connection will not slacken or overheat under normal conditions of use. For polarity-dependant VWD, reverse connection shall initiate a fault at the CIE and not damage the VWD.AS 1603.11 pdf download.

Download It Now Download Here
ATTENTION: I REALLY NEED YOUR SUPPORT.THANKS A LOT.
AS NZS 60598.2.17:2019 AS pdf free download

AS NZS 60598.2.17:2019

AS NZS 60598.2.17:2019 pdf free.Luminaires Part 2.17: Particular requirements—Luminaires for stage lighting, television and film studios (outdoor and indoor). 17.7.2 The luminaires for certain types of high-intensity discharge lamp, where an explosion risk is declared by the lamp manufacturer, shall incorporate a device to prevent immediate access to the lamp after switching-off or shall be marked in accordance with the...
Download
AS NZS 4859.1:2018 AS pdf free download

AS NZS 4859.1:2018

AS NZS 4859.1:2018 pdf free.Thermal insulation materials for buildings Part 1: General criteria and technical provisions. 2.1 GENERAL This Section provides performance criteria and technical provisions for materials to be used in the thermal insulation of buildings and building services. In addition to this Section the insulating material shall— (a) meet packaging and labelling requirements of Section 3; (b) where...
Download
AS NZS 2442.2:2021 AS pdf free download

AS NZS 2442.2:2021

AS NZS 2442.2:2021 pdf free.Performance of household electrical appliances一Rotary clothes dryers Part 2: Energy efficiency labelling requirements. Section 2 Test requirements, calculations and algorithms for the energy rating label 2.1 General This Section sets out the test requirements, equations and procedures br calculating values of the comparative energy consumption (CEC), and star rating, which appear on an energy rating label....