AS 1603.13:2018 pdf download – Duct sampling smoke detectors

09-07 comment

AS 1603.13:2018 pdf download.Automatic fire detection and alarm systems Part 13: Duct sampling smoke detectors.
3.2 Electrical requirements
3.2.1 Electrical safety
Where the maximum working voltage exceeds extra-low voltage (ELy), the DSE shall conform with the
appropriate requirements of AS/NZS 3100.
3.3 Connecting facilities
The means of connection shall not permit disconnection of the DSE or its associated detector without initiating a fault or alarm signal at the control and indicating equipment (CIE). Where this requirement can be achieved without providing separate terminations for each incoming and outgoing conductor, such alternative means of connection shall be considered satisfactory. This requirement includes any arrangement by which the DSE can be detached from its terminating facility.
The terminations shall be designed so conductors connected thereto can be rigidly and effectively clamped between metal surfaces, or soldered, to ensure the connection made will not slacken or overheat under normal conditions of use.
For polarity sensitive DSEs, reverse connection shall initiate a fault or alarm signal but not damage the DSE.
Any termination shall be of such size as will appropriately accommodate the number and size of conductors required for the connection of the DSE.
NOTE The following are typical methods of connection:
(a) A terminal screw for each conductor.
(b) Single screw and clamp with saddle providing at least two routes for each conductor.
(c) Conductors soldered individually and separate on the termination.
3.4 Indicating facilities
Visual alarm indicators shall be red. No other indicator shall be red except that the visual alarm indicator may blink to indicate that the device is operational. A required visual alarm indicator shall conform with the requirements of AS 7240.7.
Where a remote indicating facility is provided, the failure of the remote indicator, a short circuit or an open circuit shall not prejudice the alarm operation of the smoke detector.
3.5 Enclosures
The DSE enclosure shall be designed so that normal handling during installation and service cannot cause damage which would adversely affect its performance. AS 1603.13 pdf download.

Download It Now Download Here
ATTENTION: I REALLY NEED YOUR SUPPORT.THANKS A LOT.
AS NZS 60598.2.17:2019 AS pdf free download

AS NZS 60598.2.17:2019

AS NZS 60598.2.17:2019 pdf free.Luminaires Part 2.17: Particular requirements—Luminaires for stage lighting, television and film studios (outdoor and indoor). 17.7.2 The luminaires for certain types of high-intensity discharge lamp, where an explosion risk is declared by the lamp manufacturer, shall incorporate a device to prevent immediate access to the lamp after switching-off or shall be marked in accordance with the...
Download
AS NZS 4859.1:2018 AS pdf free download

AS NZS 4859.1:2018

AS NZS 4859.1:2018 pdf free.Thermal insulation materials for buildings Part 1: General criteria and technical provisions. 2.1 GENERAL This Section provides performance criteria and technical provisions for materials to be used in the thermal insulation of buildings and building services. In addition to this Section the insulating material shall— (a) meet packaging and labelling requirements of Section 3; (b) where...
Download
AS NZS 2442.2:2021 AS pdf free download

AS NZS 2442.2:2021

AS NZS 2442.2:2021 pdf free.Performance of household electrical appliances一Rotary clothes dryers Part 2: Energy efficiency labelling requirements. Section 2 Test requirements, calculations and algorithms for the energy rating label 2.1 General This Section sets out the test requirements, equations and procedures br calculating values of the comparative energy consumption (CEC), and star rating, which appear on an energy rating label....
Download

LEAVE A REPLY

Anonymous netizen Fill in information