AS 3011.2:2019 pdf free – Part 2: Sealed cells

09-02 comment

AS 3011.2:2019 pdf free.Electrical installations一Secondary batteries installed in buildings Part 2: Sealed cells.
2.2.6 Luminaires
Battery room lighting shall be installed in accordance with AS/NZS 1680.1. Luminaires shall be installed in the middle of aisles and at a minimum distance of 200 mm from any part of a battery. Luminaires shall be a fully enclosed fitting. Luminaires shall not be installed directly over a cell or an exposed live part.
2.2.7 Location of general purpose outlets
General purpose outlets shall be located at least 1 800 mm from the battery and a minimum of 100 mm
below the lowest point of the highest ventilation opening.
2.3 Battery enclosure requirements
2.3.1 Enclosure construction
Where an enclosure is designed to accommodate a battery charger and other equipment as well as a battery, a separate compartment shall be provided for the battery. The enclosure shall be lockable.
NOTE The ventilation openings for the compartments should be spaced as per the recommendations of AS 2676.2.
2.3.2 Take-off battery terminals and outgoing busbars and cables
Outgoing cables shall be fully insulated. Take-off battery terminals and busbar connections shall —
(a) be shrouded or be protected by insulating barriers to prevent accidental contact; and
(b) have their polarity clearly identified.
2.3.3 Battery compartment circuits
Only circuits associated with a battery shall be installed within a battery compartment of an enclosure.
3 Installation
3.1 General
The prospective short-circuit current of the battery, in accordance with the battery manufacturer’s specifications, shall be determined when designing the battery installation. In particular, this applies to the connection from the battery to the main d.c. switchboard or associated equipment. The installation shall conform to AS/NZS 3000.
3.2 Connections
A battery and any busbar system shall be connected by an insulated flexible connection rated to carry the maximum prospective short circuit current and the maximum load current in installations where vibration levels exceed manufacturer’s specified limits. In other installations, batteries and busbar systems may be connected by solid links or flexible cables, rated as above, and connected directly to the battery terminals.AS 3011.2 pdf download.

Download It Now Download Here
ATTENTION: I REALLY NEED YOUR SUPPORT.THANKS A LOT.
AS NZS 60598.2.17:2019 AS pdf free download

AS NZS 60598.2.17:2019

AS NZS 60598.2.17:2019 pdf free.Luminaires Part 2.17: Particular requirements—Luminaires for stage lighting, television and film studios (outdoor and indoor). 17.7.2 The luminaires for certain types of high-intensity discharge lamp, where an explosion risk is declared by the lamp manufacturer, shall incorporate a device to prevent immediate access to the lamp after switching-off or shall be marked in accordance with the...
Download
AS NZS 4859.1:2018 AS pdf free download

AS NZS 4859.1:2018

AS NZS 4859.1:2018 pdf free.Thermal insulation materials for buildings Part 1: General criteria and technical provisions. 2.1 GENERAL This Section provides performance criteria and technical provisions for materials to be used in the thermal insulation of buildings and building services. In addition to this Section the insulating material shall— (a) meet packaging and labelling requirements of Section 3; (b) where...
Download
AS NZS 2442.2:2021 AS pdf free download

AS NZS 2442.2:2021

AS NZS 2442.2:2021 pdf free.Performance of household electrical appliances一Rotary clothes dryers Part 2: Energy efficiency labelling requirements. Section 2 Test requirements, calculations and algorithms for the energy rating label 2.1 General This Section sets out the test requirements, equations and procedures br calculating values of the comparative energy consumption (CEC), and star rating, which appear on an energy rating label....