AS 4428.3:2020 pdf free.Fire detection, warning, control and intercom systems — Control and indicating equipment Part 3: Fire brigade panel.
2.1 General
FBPs shall meet the requirements of this Section, and the requirements and tests set out in AS 7240.2. The requirements in this Section shall be verified by visual inspection or engineering assessment as appropriate.
In addition, the following shall apply:
(a) The indicators and controls shall be enclosed within an FBP frame as shown in Figures 2.1 or 2.3.
(b) No other indicators and controls shall be within the FBP frame except as detailed in this Standard.
Functions and indications on the FBP and FDCIE shall be consistent so that contradicting information does not occur.
2.2 Indicators and controls
2.2.1 General
Controls and indicators shall be provided and labelled in accordance with Table 2.1.
Non-addressable fire detection zones in alarm shall be indicated by means of a separate light-emitting indicator for each zone or on an alphanumeric display, or both.
Addressable points in alarm shall be individually indicated on an alphanumeric display. Labelling may be in upper case, lower case, or any combination thereof.
2.2.2 General fire alarm indicator
A general fire alarm condition shall be indicated without prior manual intervention by means of the separate light-emitting indicator a. The general fire alarm indicator a shall be labelled “FIRE”.
2.2.3 FBP using alphanumeric alarm display
The following shall apply to indicators and controls of an FBP using an alphanumeric display:
(a) No other indicators within the FBP frame shall be above or to the left of the general fire alarm indicator, except for display b.
(b) Indicators and controls shall be wholly within equally sized fields as specified in Table 2.1 and in accordance with Figure 2.2.
NOTE 1 Where several fields are permitted, the indicators and controls may be placed across all listed fields.
The labelling shall be clearly associated with the indicators and controls, but need not be wholly within the fields specified in Table 2.1.
NOTE 2 Figure 2.1(a) and (b) shows examples of the layout of controls and indicators on an FBP.
(c) Fire detection zones and addressable points in alarm and their location descriptor shall be shown in display b.AS 4428.3 pdf download.
AS 4428.3:2020 pdf free
ATTENTION:
I REALLY NEED YOUR SUPPORT.THANKS A LOT.