AS 7240.22:2018 pdf free

09-07 comment

AS 7240.22:2018 pdf free.Fire detection and alarm systems Part 22: Smoke-detection equipment for ducts (ISO 7240-22:2017, MOD).
4.5 Manufacturer’s adjustments
It shall not be possible to change the manufacturer’s settings except by special means (e.g. the use of a special code or tool) or by breaking or removing a seal.
4.6 On-site adjustment of response behaviour
4.6.1 If there is provision for on-site adjustment of the response behaviour of the SDED, then
a) for all of the settings at which the manufacturer claims compliance with this document, the SDED shall comply with the requirements of this document and access to the adjustment means shall be possible only by the use of a code or special tool or by removing the SDED from its base or mounting;
b) any setting(s) at which the manufacturer does not claim compliance with this document shall be accessible only by the use of a code or special tool, and it shall be clearly marked on the SDED or in the associated data that if these setting(s) are used, the SDED does not comply with this document.
4.6.2 These adjustments may be carried out at the SDED, the detector or the control and indicating equipment.
4.7 Requirements for software-controlled smoke-detection equipment for ducts
4.7.1 General
The requirements of 4.7.2 and 4.7.3 shall be met for SDED that rely on software control in order to fulfil the requirements of this document.
4.7.2 Software design
In order to ensure the reliability of the SDED, the following requirements for software design shall apply.
a) The software shall have a modular structure.
b) The design of the interfaces for manually and automatically generated data shall not permit invalid data to cause an error in the program operation.
c) The software shall be designed to avoid the occurrence of deadlock of the program flow.
4.7.3 Storage of programs and data
4.7.3.1 The program necessary to comply with this document and any preset data, such as manufacturer’s settings, shall be held in non-volatile memory. Writing to areas of memory containing this program and data shall be possible only by the use of some special tool or code and shall not be possible during normal operation of the detector.AS 7240.22 pdf download.

Download It Now Download Here
ATTENTION: I REALLY NEED YOUR SUPPORT.THANKS A LOT.
AS NZS 60598.2.17:2019 AS pdf free download

AS NZS 60598.2.17:2019

AS NZS 60598.2.17:2019 pdf free.Luminaires Part 2.17: Particular requirements—Luminaires for stage lighting, television and film studios (outdoor and indoor). 17.7.2 The luminaires for certain types of high-intensity discharge lamp, where an explosion risk is declared by the lamp manufacturer, shall incorporate a device to prevent immediate access to the lamp after switching-off or shall be marked in accordance with the...
Download
AS NZS 4859.1:2018 AS pdf free download

AS NZS 4859.1:2018

AS NZS 4859.1:2018 pdf free.Thermal insulation materials for buildings Part 1: General criteria and technical provisions. 2.1 GENERAL This Section provides performance criteria and technical provisions for materials to be used in the thermal insulation of buildings and building services. In addition to this Section the insulating material shall— (a) meet packaging and labelling requirements of Section 3; (b) where...
Download
AS NZS 2442.2:2021 AS pdf free download

AS NZS 2442.2:2021

AS NZS 2442.2:2021 pdf free.Performance of household electrical appliances一Rotary clothes dryers Part 2: Energy efficiency labelling requirements. Section 2 Test requirements, calculations and algorithms for the energy rating label 2.1 General This Section sets out the test requirements, equations and procedures br calculating values of the comparative energy consumption (CEC), and star rating, which appear on an energy rating label....
Download

LEAVE A REPLY

Anonymous netizen Fill in information