IEEE 48-1975 pdf free

04-25 comment

IEEE 48-1975 pdf free.IEEE Standard Test Procedures and Requirements for High-Voltage Alternating-Current Cable Terminations.
IEEE 48 covers all indoor and outdoor cable terminations used on alternating-current cables having laminated or extruded insulation rated 2.5 kV through 500 kV, except separable insulated connectors which are covered by 111.
Cable terminations and component parts shall be capable of withstanding the tests specified in this standard.
The rating of a high-voltage cable termination shall include the following items. where applicable:
BIL (basic lightning impulse insulation level). The crest value of a lightning impulse voltage of a specified wave shape which the high-voltage cable termination is required to withstand under specified conditions.
BSL (basic switching impulse insulation level). The crest value of a switching impulse voltage of a specified wave shape which the high-voltage cable termination is required to withstand under specified conditions.
insulation class. The nominal phase-to-phase operating voltage of a three-phase cable systern where the device may be applied, and reflects the associated design tests and impulse insulation levels.
maximum and minimum cable conductor diameter. The largest and smallest cable conductor diameters that the high-voltage cable termination is designed to accommodate without special modifications.
maximum and minimum cable insulation diameter. The largest and smallest diameters over the insulation of round conductor cables. as measured by a circumferential tape, that the high-voltage cable termination is designed to accommodate without special modifications.
maximum design voltage to ground. The maximum voltage at which the high voltage cable termination is designed to operate continuously under normal conditions.
NOTE: It is not intended that this maximum voltage limit be applied to transient overvoltages or unusual service operating conditions where the system voltage may exceed those values for only short periods of time.

Download It Now Download Here
ATTENTION: I REALLY NEED YOUR SUPPORT.THANKS A LOT.

IEEE 82-2002 pdf free

IEEE 82-2002 pdf free.IEEE Standard Test Procedure for Impulse Voltage Tests on Insulated Conductors. Insulated conductors in service are subjected to voltage surges from lightning. switching, and other sources. These surges vary widely in wave shape, magnitude. and frequency of occurrence. Laboratory tests cannot duplicate the wide variety of surges met in service. Standard test procedures. however, make it possible...
Download

IEEE 475-2000 pdf free

IEEE 475-2000 pdf free.IEEE Standard Measurement Procedure for Field Disturbance Sensors 300 MHz to 40 GHz. Abstract: Test procedures for microwave field disturbance sensors to measure radio frequency RF) radiated field strength of the fundamental frequency, harmonic frequencies, near field power flux density, and nonharmonic spurious emissions of sensors operating within the frequency range of 300 MHz to 40 GHz...
Download

IEEE 1277-2000 pdf free

IEEE 1277-2000 pdf free.IEEE Standard General Requirements and Test Code for Dry-Type and Oil-Immersed Smoothing Reactors for DC Power Transmission. Abstract: The electrical, mechanical, and physical requirements of oil-immersed and dry-type air core smoothing reactors for high-voltage direct current( HVDC)applications are specified. Test code is defined and appropriate technical background information is presented or identified. Keywords: construction, dry-type air core,...
Download

LEAVE A REPLY

Anonymous netizen Fill in information